        DynAmp LKP

        DynAmp LKP

        The LKP-30 is a high accuracy, “closed-loop” Hall effect system designed to accurately and reliably measure unidirectional dc bus currents up to 30 k amperes. This “system” consists of a two-piece measuring head, which installs around the bus, an electronics unit and two multiconductor cables connecting the two.


        Application

        The LKP-30 is particularly well suited to measure individual as well as total bus currents in Electro-chemical processes including aluminum, chlorine, copper, manganese, titanium, zinc as well as electroplating and coating processes.

         

        Specifications

        Input

        Full Scale (FS) bus current 30 kA

        Based on approved DynAmp Bus Analysis

        Output

        Voltage scaling 10 mV per bus kA

        Voltage full scale 300 mV

        Voltage accuracy ± 0.1% of FS **

        Current scaling 200 mA per bus kA

        Current full scale 6 A

        Current loop max burden 15 V

        Current accuracy ± 0.1% of FS ** Repeatability ± 0.02% of FS

        plus core set

        Linearity (5...100% of FS) ± 0.03% of FS

        Temperature sensitivity ± 0.002% of FS per oC

        Mains

        Available Input Ranges 100V: 85 to 110V RMS

        120V: 102 to 132V RMS

        200V: 170 to 220V RMS

        220V: 187 to 242V RMS

        240V: 204 to 264V RMS

        Frequency 50Hz.: 45 to 55 Hz.

        60Hz.: 55 to 65 Hz.

        Power requirements 20 VA / bus kA typical

        Impact of mains variation 100, 120, and 200V:

        on accuracy ± 0.001% FS / V RMS

        220, 240V:

        ± 0.0005% FS / VRMS

        Isolation

        Bus to output 6 kVac for 1 minute with

        25 mm air gap

        Mains supply to output 1.5 kVac for 1 minute

        Mains supply to chassis 1.5 kVac for 1 minute

        Output to chassis 1.5 kVac for 1 minute

        Bus to head structure 6 kVac for 1 minute with

        25 mm air gap

        Environmental

        Operating temperature -4° to 130° F

        -20° to 55° C

        Storage temperature -4° to 150° F

        -20° to 65° C

        Installation Restrictions: Ref. Tech. Bulletin 990

        Physical

        Measuring head enclosure IP-649

        Measuring head weight 139 lbs. / 63 kg

        Electronics unit enclosure IP-20

        Electronics unit weight 62 lbs. / 28 kg (Max.)

        Interconnecting cable(s) 33 Ft / 10 m standard

        (Head to Meter Unit) 2 cables

        ** At DynAmp reference conditions:

        77° F ± 4° F (25o C, ± 2o C)

        120/240 V RMS. ± 2%, 60 Hz + 1Hz.